Dallas Energy Inspections

Energy Inspections for The City of Dallas Building Code

Residential  Energy Inspection Checklist

The following are a list of requirements that must be complied with to be compliant with the Dallas Energy Code. Most Energy Code requirements are prescriptive however there are provisions for trade offs using the Performance Path to Compliance. This requires a Building Energy Analysis to gather enough data to provide for energy tradeoffs using computer software.  The Building Energy Analysis is a useful option to limit construction cost or solve a compliance problem. There is an additional fee for this service.

Requirements

  • Inspection Schedule
    IECC 105.2    Required Approvals
    The city of Dallas requires a finish frame inspection after the wall insulation is installed and before the sheetrock is installed. They also require a final insulation inspection after the ceiling insulation and mechanical HVAC equipment is installed. The energy certification is required by the City of Dallas Building Department before the final Electrical inspection is approved.
  • Ceiling Insulation
    IECC 102.1.1.1    Marker installation
    Fiberglass or cellulose insulation must have thickness markers installed every 300 square feet in the attic space. These markers shall be be written in inches and face towards the attic access opening
  • Climate Zone
    IECC 301.2(1)    Warm Humid Counties for Texas
    The City of Dallas in conjunction with the North Texas Council of Governments (NTCOG) has designated the Dallas / Ft Worth Metroplex area as a Zone 3.2 designation
  • Insulation and Fenestration criteria
    IECC 402.1.1 General Prescriptive criteria
    This section establishes various criteria based on a ratio of window glazing area to wall surface area. The different criteria ratios are 15%, 20%, 25% and 30% or more . The more window glazing areas require a higher wall and ceiling insulation value and lower U-Factor and Solar Heat Gain Coefficient (SHGC). This section also allows a limited area of cathedral ceiling insulation values to be decreased if other areas have increased insulation values. Pier and beam crawl space floor requires R-19 insulation values.
  • Air Leakage
    IECC 402.4.1 Building Thermal Envelope
    The building thermal envelope will be durably sealed to limit air infiltration with caulk, gaskets, weather stripping or an air barrier material.
  • Air Leakage
    IECC 402.4.2 Recessed Lighting
    IC-rated enclosures that are sealed and gasketed to prevent air leakage from the living area to the attic area are to be used. Non IC-rated enclosures will need an airtight sealed box with clearance of at least .5 inches from combustion able materials and 3 inches from insulation.
  • Mechanical Systems - Mandatory
    IECC 403.2 HVAC Ducts
    All HVAC supply and return ducts will be insulated to R-8 if they are located outside the building thermal envelope. R-6 ducts are allowed in floor trusses. R-6 insulated ducts are allowed outside the building thermal envelope if the air conditioning equipment is upgrade 1 SEER point above the minimum acceptable value (currently SEER 13).
  • Mechanical Systems - Mandatory
    IECC 403.2.2 Duct Sealing
    All duct joints and seams, air handlers and filter boxes  will be sealed with mastic. 
  • Mechanical Systems - Mandatory
    IECC 403.2.3  Building Cavities
    Building cavities  will not be used as supply ducts.
  • Mechanical Systems - Mandatory
    IECC 403.3 Mechanical System piping insulation
    Mechanical system piping that is capable of carrying fluids above 105 degrees or below 55 degrees will be insulated to at least R-2.
  • Mechanical Systems - Mandatory
    IECC 403.4 Circulating Water Systems
    All circulating service hot water piping will be insulated to at least R-2.

Insulation